Optimasi Penentuan Lokasi Switched 20 KV Power Capacitors Pada Jaringan Distribusi 20 KV Jawa Timur

Emmy Hosea • Adi Nugraha
Journal article Jurnal Teknik Elektro Universitas Kristen Petra • September 2001 Indonesia

Abstract

Since 1993%2C PLN Jawa Timur found that it is necessary to apply power capacitors in the primary distribution feeders because the power factor and voltage along the main distribution line remain low. It is expected that with the application of power capacitors to fix power factor and voltage%2C then energy losses along the primary distribution feeders could be reduced .This paper will analyze and study about the implementation and USAge of 20 KV power capacitors on the primary distribution feeders%2C and also optimize the correct placement of power capacitors on 20 KV primary distribution feeder belongs to PLN Jawa Timur. From the optimization process to correctly place the power capacitors on case study Jatirogo feeders it was found that the most efficient and effective place to attach the power capacitors is on T - 672 using 900 kVAR power capacitors which attain cos f %3D 0%2C9979 and voltage rise up to 4%2C141 %25.

Metrics

  • 222 views
  • 95 downloads

Journal

Jurnal Teknik Elektro Universitas Kristen Petra

Jurnal Teknik Elektro Universitas Kristen Petra is published biannually, in May and September, by... see more