Perbaikan Stabilitas Dinamik Melalui Penjadwalan Ulang Pembangkit Menggunakan Sensitivitas Trayektori

Wellem Fridz Galla
Journal article Jurnal Teknik Elektro Universitas Kristen Petra • September 2006 Indonesia

Abstract

The optimum operation condition of power system obtained from optimal calculation is determined without considering its dynamic stability limit. If the load of system is changed, power generating should accommodate the changes to make the demand of load supplied. This changing will shift dynamic stability system condition. This article deals with dynamic stability correction as a result of load of system changing by generation rescheduling using the biggest sensitivity of the sensitivity trajectory variable with respect to its parameters i.e. the power out put generators. The simulation in the 3-machines 9 bus power system with 25%, 50% and 75% load increasing of initial load caused eigen value position better, 1,2 and 3,4 of 25% load increasing each of them is 1,1 x 10-5 and 0,5 x 10-5, to 50% load increasing is 3,47 x 10-4 and 0,98 x 10-4, to 75% load increasing is 1,11 x 10-4 and 1,67 x 10-4 more far from imaginary axis compare to before generating rescheduling. The simulation result with this method indicates that there is dynamic stability correction, in this manner the system operates with better dynamic stability condition.

Metrics

  • 168 views
  • 115 downloads

Journal

Jurnal Teknik Elektro Universitas Kristen Petra

Jurnal Teknik Elektro Universitas Kristen Petra is published biannually, in May and September, by... see more